ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
Honeywell Xtralis VESDA Sensepoint XCL Gas Detector
Honeywell logoDealer for Honeywell

Honeywell Xtralis VESDA Sensepoint XCL Gas Detector

VESDAGas detectorBluetoothIP654-20 mA or Modbus

A gas detector in the VESDA range that gives early warning of gases for occupant protection and system monitoring, alongside protection against fire. Its built-in Bluetooth pairs with a smart device app for installation, commissioning and maintenance.

  • Embedded Bluetooth for app-based setup, commissioning and maintenance
  • Supply 11 to 32 V DC with analog 4-20 mA output, or 9 to 32 V DC with Modbus; 24 VAC nominal also listed
  • IP65, Type 4 (NEMA 250) polycarbonate casing in charcoal colour
  • Operating temperature -20 to +50 °C, humidity 0 to 99% non-condensing
  • Pluggable rising clamp terminals for 0.5 to 1.5 mm2 wire
  • Listed standards: IEC 61010-1, EN 50270, UL 2075, CE and FCC

Standards and approvals: IEC61010-1, CE, EN 50270, FCC, UL2075

Ask price & availability

Download the official Honeywell catalogue (PDF, 17.2 MB)

Specifications

Specifications
SpecificationDetails
Supply Voltage24 VDC nominal | 11 to 32V DC (Analog 4-20 mA) | 9 to 32V DC (Modbus) | 24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum Power Consumption (24V DC)1.2 W (Analog 4-20mA) (toxic), 1.7W (flammable and CO2) | 0.7 W (Modbus) (toxic), 1.2W (flammable and CO2) | Relay Version: additional 0.6W total
Maximum Inrush Current (24V DC)850 mA
Dimensions (WxHxD)113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in)
Weight500 g (1.1 lb)
Ingress Protection RatingIP65, Type 4 (NEMA 250)
Casing MaterialPolycarbonate (charcoal colour)
Operating ConditionsOperating Temperature: −20 to +50 °C (−4 to +122 °F) | Storage Temperature: 0 to +30 °C (+32 to +86 °F) | Humidity: 0 to 99% (non-condensing) | Flammable catalytic versions: 10 to 90% RH. Operating the detector outside this range may result in increased drift and a reduction in detector accuracy. | Atmospheric pressure: 95 to 110 kPa
Wire/Terminal sizePluggable rising clamp style. | 0.5 to 1.5 mm2, 20 to 16 AWG.
OutputAnalog Output: 0 to 22 mA | Digital Output: Modbus RTU | Relay Output: 2 relays (24 V DC / 240 V | AC, 5 A)

Specifications as published by Honeywell. Please confirm the exact model with us before ordering.