ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
Tyco
Tyco logoSupplier for Tyco

Tyco Model TY7258 Standard Response Pendent and Recessed Pendent Sprinkler, K16.8, Specific Use (TFP337)

PendentK16.8RetrofitSpecific useTFP337

A K16.8 standard response pendent for a specific end use retrofit, fire tested at full scale at UL LLC for shelf display and rack storage of cartoned Group A plastic.

  • Test results verified by UL in report NC27954
  • Design criteria follow NFPA 13 (2022 edition) section 24.1.7
  • Pendent and recessed pendent versions, 3/4 in. NPT
  • Temperature ratings 68°C and 93°C; maximum working pressure 175 psi (12.1 bar)
  • Approval details are given through UL's online verification service
Ask price & availability

Download the official Tyco catalogue (PDF, 4.6 MB)

Specifications

Specifications
SpecificationK=16.8 gpm/psi½ (241,9 Lpm/bar½)TY7258
FrameBrass
DeflectorBronze
Compression ScrewBrass
Bulb (5 mm)Glass
ButtonBrass
SINTY7258
K-factor16.8 K-factor
Pipe Thread Connection3/4 in. NPT
ResponseStandard Response
Discharge CoefficientK=16.8 gpm/psi½ (241,9 Lpm/bar½)
Maximum Working Pressure175 psi (12,1 bar)
Temperature Ratings155°F (68°C), 200°F (93°C)
FinishSprinkler: Natural Brass, Signal White, Bright Chrome Separately Ordered Escutcheon: Brass Plated, Signal White, Chrome Plated
ApprovalsFor complete details refer to: https://verify.ul.com/verifications/105

Specifications as published by Tyco. Please confirm the exact model with us before ordering.

More Tyco ESFR and Storage Sprinklers

Fire Sprinklers from other brands

Savemax

Savemax Flexible Drop for Sprinklers (700 to 1800 mm)

Flexible dropSprinkler connector700 to 1800 mm

A flexible hose connector that links the rigid sprinkler branch pipe above a false ceiling to the sprinkler head below it. It takes up building movement, ceiling deflection and installation misalignment, so the head can be positioned without cutting or re-routing pipe.

View specifications ›

See all fire sprinklers ›

Ask price
Call +91 92440 89060Send a text messageEmail usWhatsApp us