ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
Tyco Series LFII Residential Pendent, Recessed Pendent and Concealed Pendent Sprinkler (TY4234), K6.9, NFPA 13 Optimized (TFP408)
Tyco logoSupplier for Tyco

Tyco Series LFII Residential Pendent, Recessed Pendent and Concealed Pendent Sprinkler (TY4234), K6.9, NFPA 13 Optimized (TFP408)

ResidentialK6.9NFPA 13 optimizedUL, C-ULTFP408

A large K6.9 fast response residential sprinkler for NFPA 13 designs that need higher flows, also usable in wet pipe NFPA 13D and 13R systems.

  • K-factor 6.9 gpm/psi½ (99.4 Lpm/bar½), 3/4 in. NPT thread
  • Pendent, recessed pendent (two-piece Style 30 escutcheon) and concealed pendent versions
  • Pendent and recessed pendent at 68°C or 79°C; concealed at 68°C with a 59°C cover plate, for ceilings up to 38°C
  • Concealed version has a push-on, thread-off design with 1/2 in. of vertical adjustment
  • Maximum working pressure 175 psi (12.1 bar)
  • Tyco lists UL and C-UL listing

Standards and approvals: UL and C-UL Listed

Ask price & availability

Download the official Tyco catalogue (PDF, 4.6 MB)

Specifications

Specifications
SpecificationK=6.9 gpm/psi½ (99,4 Lpm/bar½)TY4234
FrameBrass
ButtonCopper
SINTY4234
K-factor6.9 K-factor
Pipe Thread Connection3/4 in. NPT Sprinkler Temperature Rating Pendent and Recessed Pendent: 155°F (68°C) or 175°F (79°C) Concealed Pendent: 155°F (68°C) w/139°F (59°C) Cover Plate* * Suitable for use with maximum 100°F (38°C) ceiling temperature.
Discharge CoefficientK=6.9 gpm/psi½ (99,4 Lpm/bar½)
Maximum Working Pressure175 psi (12,1 bar)
Finishes• Sprinkler:

Specifications as published by Tyco. Please confirm the exact model with us before ordering.

More Tyco Residential Sprinklers

Fire Sprinklers from other brands

Savemax

Savemax Flexible Drop for Sprinklers (700 to 1800 mm)

Flexible dropSprinkler connector700 to 1800 mm

A flexible hose connector that links the rigid sprinkler branch pipe above a false ceiling to the sprinkler head below it. It takes up building movement, ceiling deflection and installation misalignment, so the head can be positioned without cutting or re-routing pipe.

View specifications ›

See all fire sprinklers ›

Ask price
Call +91 92440 89060Send a text messageEmail usWhatsApp us