Notifier FSP-951 Intelligent Photoelectric Smoke Detector
An intelligent addressable photoelectric smoke detector with an optical chamber that senses smoke from a wide range of fires, and sensitivity that is programmable and monitored by the panel.

Dealer for NotifierAn intelligent photoelectric smoke detector with dual thermistors that add 135°F (57°C) fixed temperature heat sensing in the same head.
Standards and approvals: UL/ULC Listed: S911, FM Approved, CSFM: 7272-0028:0503
| Specification | Details | Details |
|---|---|---|
| Sensitivity | • UL Applications: 0.5% to 4.0% per foot obscuration. • ULC Applications: 0.5% to 3.5% per foot obscuration. | |
| Size | 2.0" (5.3 cm) high; base determines diameter.: B300-6: 6.1" (15.6 cm) diameter., B501: 4" (10.2 cm) diameter. | |
| Shipping weight | 3.4oz (96.4g) | |
| Operating Temperature range | • FSP-951, 0°C to 50°C (32°F to 122°F). • FSP-951T, 0°C to 38°C (32°F to 100°F). • FSP-951R installed in a DNR/DNRW, -20°C to 70°C (-4°F to 158°F). | |
| UL/ULC Listed Velocity Range | 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts. | |
| Relative Humidity | 10%-93% noncondensing. | |
| Thermal Ratings | Fixed-temperature setpoint 135°F (57°C). | |
| Voltage Range | 15-32 volts DC peak. | |
| Standby Current (max. avg.) | 200μA @ 24VDC (one communica- tion every five seconds with LED enabled). | |
| LED Current (max.) | 4.5mA @ 24 VDC (“ON”). |
Specifications as published by Notifier. Please confirm the exact model with us before ordering.
An intelligent addressable photoelectric smoke detector with an optical chamber that senses smoke from a wide range of fires, and sensitivity that is programmable and monitored by the panel.
An intelligent addressable heat detector that uses a thermistor sensing circuit for 135°F (57°C) fixed temperature detection.
A low-profile intelligent addressable heat detector that responds to a rate of temperature rise of 15°F (8.3°C) per minute.
An intelligent addressable heat detector with a thermistor sensing circuit, factory preset to 190°F (88°C) for high temperature detection.
An intelligent plug-in photoelectric smoke detector with a built-in isolator, for FlashScan systems only.
An intelligent photoelectric smoke detector with 135°F (57°C) fixed heat sensing and positive side isolation on the SLC, used with an isolation base, for FlashScan systems only.
A battery operated, Wi-Fi enabled photoelectric smoke detector from the IMPACT by Honeywell range. When smoke reaches its alarm threshold it sounds a buzzer, flashes an LED and sends real-time alerts to a smartphone through the IMPACT by Honeywell app.
A battery operated standalone smoke alarm with photoelectric sensing that sounds an alarm and lights a red LED when smoke reaches its threshold. It runs on two AA batteries and also warns of a low battery or a chamber fault.
An S200A plug-in photoelectric smoke detector listed with the DXc and ZXSe panels. Its detection chamber is designed to cut false alarms from dust, insects and other debris.
An S200A multi-criteria detector that adds 58°C fixed temperature and rate of rise thermal sensing to a photoelectric smoke sensor, for better false alarm immunity and faster response to a wide range of fires.
A white addressable photoelectric smoke detector working on the light scattering principle, with smoothing filters and embedded software to resist unwanted alarms. The 22051EI version has a built-in isolator.
A two sensor detector that adds thermal sensing to the photoelectric smoke chamber for better false alarm immunity and a faster response to a wide range of fires. The 22051TEI version has a built-in isolator.