ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
System Sensor InnovairFlex D2 2-Wire Photoelectric Duct Smoke Detector
Dealer for System Sensor

System Sensor InnovairFlex D2 2-Wire Photoelectric Duct Smoke Detector

D2InnovairFlex2-wirePhotoelectric

A 2-wire photoelectric duct smoke detector with a pivoting housing that fits square or rectangular footprints on round or rectangular ductwork.

  • Air velocity 100 to 4,000 ft/min (0.5 to 20.32 m/sec)
  • Power supply 8.5 to 35 VDC
  • Plug-in sensor with integrated low-flow technology
  • Sampling tube installs from the front or back without tools
  • Cover tamper feature and a ¾ inch conduit knockout for extra wiring space
  • Operating temperature -20 to 70°C, weight 0.82 kg
Ask price & availability

Specifications

Specifications
SpecificationD2
Weight:1.8 lb (0.82 kg)
Operating Temperature Range:-4°F to 158°F (-20°C to 70°C)
Storage Temperature Range:-22°F to 158°F (-30°C to 70°C)
Operating Humidity Range:0% to 95% relative humidity non-condensing
Air Duct Velocity:100 to 4000 ft/min (0.5 to 20.32 m/sec)
Power supply voltage:8.5-35 VDC
Input capacitance:0.1 µF max.
Reset voltage:2.5 VDC min.
Reset time: (with RTS451)0.03 to 0.3 sec.
Reset time: (by power down)0.3 sec. max.
Power up time:35 sec. max.
Alarm response time:15 sec.
Sensitivity Test:See detector label
Peak standby current:120µA
Max. standby current:60 µA (average)
Max. alarm current:130 mA

Specifications as published by System Sensor. Please confirm the exact model with us before ordering.

More System Sensor Duct Smoke Detectors

Beam, Flame and Special Detectors from other brands

See all beam, flame and special detectors ›

Ask price