ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
Apollo Orbis Heat Detector, Class A1R
Apollo logoAuthorised distributor for Apollo

Apollo Orbis Heat Detector, Class A1R

ORB-HT-11001-APOHeat A1ROrbisRate of rise

An Orbis conventional heat detector in class A1R: the lowest temperature band, with rate of rise response. A single thermistor gives an output that follows the air temperature, for areas where smoke detectors are unsuitable.

  • For dirty or smoky environments
  • Red flashing LED at start up, yellow SensAlert LED for faults
  • FasTest check in four seconds
  • VdS, LPCB, FG, BOSEC, SBSC and CPR approvals
  • 95 μA quiescent current, -40 to 70°C, IP23D
  • 10 year warranty

Standards and approvals: VdS, LPCB, FG, BOSEC, SBSC, CPR

Ask price & availability

Specifications

Specifications
SpecificationORB-HT-11001-APO
Warranty10 year
ApplicationsB&Bs/guest houses, Car parks/loading bays, Dusty environments, Restaurants, Retail, Small to medium buildings
Fire TypeFast burning, flaming fires
Heat classificationA1R
ColourWhite
Weight70g
Materials housingPolycarbonate
Product length36mm | 1.42in
Product diameter97mm | 3.82in
Quiescent current95μA
Quiescent current tested at24V dc
PolarityL1 &, L2 are polarity sensitive
Minimum 'detector active' voltage6V
Holding voltage5 to 33V
Holding voltage (max)33V
Holding voltage (min)5V
Minimum voltage to light alarm LED5V
Alarm reset time1s
Alarm load600Ω
Humidity (max)98%, RH
Humidity (min)0%, RH
Humidity Noteno condensation or icing
Humidity0% to 98% (no condensation or icing)
Operating temperature-40 to 70°C | -40 to 158°F
Operating temperature (max)70°C | 158°F
Operating temperature (min)-40°C | -40°F
IP rating ValueIP23D
Storage temperature (max)70°C
Storage temperature (min)-40°C
Storage temperature-40 to 70°C

Specifications as published by Apollo. Please confirm the exact model with us before ordering.

More Apollo Conventional Detectors

Apollo Series 65 Heat Detector, Class A1R

55000-122APOHeat A1REN 54-5

A conventional heat detector that monitors temperature with a dual thermistor network, classed A1R to EN 54-5: the lowest temperature band, with rate of rise response. It suits places where smoke detectors are unsuitable, such as dirty, smoky or steamy areas.

View specifications ›

Apollo Series 65 Heat Detector, Class BR

55000-127APOHeat BREN 54-5

A conventional heat detector in class BR, for areas that run warmer than a normal room, with rate of rise response. Its dual thermistor network gives a voltage output that follows the surrounding air temperature.

View specifications ›

Apollo Series 65 Heat Detector, Class CR

55000-132APOHeat CRSeries 65

A conventional heat detector in class CR, for areas with higher normal temperatures, that also responds to a fast rise in temperature. Its dual thermistor network gives an output that follows the surrounding air temperature.

View specifications ›

Apollo Orbis Optical Smoke Detector

ORB-OP-12001-APOOptical smokeOrbis

A conventional optical smoke detector using the light scatter principle, with sensing technology designed to reduce false alarms. It responds well to slow burning, smouldering fires.

View specifications ›

Smoke and Heat Detectors from other brands

See all smoke and heat detectors ›

Ask price
Call +91 92440 89060Send a text messageEmail usWhatsApp us