ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
Siemens FC362 Cerberus FIT Addressable Fire Control Panel, 2 Loop (FC362-ZZ Compact, FC362-ZA Comfort Housing)
Siemens logoDealer for Siemens

Siemens FC362 Cerberus FIT Addressable Fire Control Panel, 2 Loop (FC362-ZZ Compact, FC362-ZA Comfort Housing)

Cerberus FIT addressable252 addresses2 loopsPanel ConfiguratorEN 54-13

A Cerberus FIT addressable panel for up to 252 devices on two loops, for smaller installations such as workshops, smaller hotels, schools, stores and residential homes.

  • Up to 252 addressed detectors and devices; 2 loops or 4 stub lines
  • Integrated Panel Configurator: set up from a PC or laptop without extra software
  • FC362-ZZ: slim compact housing for 2x 12 V, 12 Ah batteries
  • FC362-ZA: Comfort housing for 2x 12 V, 25 Ah batteries
  • Mains AC 97 to 127 V or AC 196 to 253 V; IP30; -5 to 40 °C
  • Siemens lists EN 54-2, EN 54-4, EN 54-13 and UKCA

Standards and approvals: EN 54-2, EN 54-4, EN 54-13, UKCA

Ask price & availability

Download the official Siemens catalogue (PDF, 1.8 MB)

Specifications

Specifications
SpecificationFC362-ZZFC362-ZA
Detector compatibilityCerberus™ PRO FD720 (C-NET) & Cerberus™ FIT FD360 (C-NET)Cerberus™ PRO FD720 (C-NET) & Cerberus™ FIT FD360 (C-NET)
StandardEN 54-2 , EN 54-4 , EN 54-13EN 54-2 , EN 54-4 , EN 54-13
Number of addresses252252
Number of detector linesLoops: 2 Stub lines: 4Loops: 2 Stub lines: 4
Programmable input/output44
Power consumptionAlarm power: 2.309 W, Quiet power: 2.789 W
Mains voltageAC 97...127 V AC 196...253 VAC 97...127 V AC 196...253 V
Operating voltageDC 20.5…28.6 VDC 20.5…28.6 V
Operating current2500 mA2500 mA
Power supply70 W70 W
Bypass time for emergency power supply72 h72 h
Battery capacityMax. 2x 12 V, 12 AhMax. 2x 12 V, 25 Ah
Plug-in position1 for serial interface RS232 or RS4851 for serial interface RS232 or RS485
Operating temperature-5…40 °C-5...40 °C
Storage temperature-20...+60 °C-20...+60 °C
Relative humidity≤95% rel. (no condensation)≤95% rel. (no condensation)
Protection categoryIP30IP30
Relay outputs3 NO / NC3 NO / NC
Color housing/coverLight grey, ~RAL 7035Light grey, ~RAL 7035
Dimensions (W x H x D)402 x 372 x 132 mm402 x 372 x 211 mm
Weight (without battery)5.15 kg6.34 kg

Specifications as published by Siemens. Please confirm the exact model with us before ordering.