ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
Tyco
Tyco logoSupplier for Tyco

Tyco Series TY-B and TY-FRB 10 mm Orifice Upright, Pendent and Recessed Pendent Sprinklers, ISO 7-R 3/8 (TFP670)

10 mm orificeISO 7-R 3/8 threadStandard and quick responseLPCB, VdSTFP670

Glass bulb spray sprinklers with a 10 mm orifice and a 3/8 inch ISO 7 taper thread, offered as TY-B (5 mm bulb, standard response) and TY-FRB (3 mm bulb, quick response) for systems designed to the rules recognised by the approval body.

  • K-factor 58 Lpm/bar½ (4 gpm/psi½)
  • Upright and pendent heads give a hemispherical spray pattern below the deflector
  • Recessed pendent version with a two-piece Style 70 (3/8 inch NPT) escutcheon, 12 mm of recessed adjustment and up to 20 mm in total
  • Maximum working pressure 12,1 bar (174 psi)
  • Temperature ratings printed in the data sheet: 57°C, 68°C, 79°C, 93°C and 141°C
  • Tyco lists LPCB and VdS approval

Standards and approvals: LPCB and VdS Approved

Ask price & availability

Download the official Tyco catalogue (PDF, 4.6 MB)

Specifications

Specifications
SpecificationUpright, 3 mm bulbPendent, 3 mm bulbUpright, 5 mm bulbPendent, 5 mm bulbK = 58 Lpm/bar1/2 (4 gpm/psi1/2)
SINTY2109TY2209TY2108TY2208
SIN entry as printedUpright, 3 mm bulbPendent, 3 mm bulbUpright, 5 mm bulbPendent, 5 mm bulb
OrientationUprightPendentUprightPendent
Discharge CoefficientK = 58 Lpm/bar1/2 (4 gpm/psi1/2)K = 58 Lpm/bar1/2 (4 gpm/psi1/2)K = 58 Lpm/bar1/2 (4 gpm/psi1/2)K = 58 Lpm/bar1/2 (4 gpm/psi1/2)
Maximum Working Pressure12,1 bar (174 psi)12,1 bar (174 psi)12,1 bar (174 psi)12,1 bar (174 psi)
Temperature RatingSee Table ASee Table ASee Table ASee Table A
FinishesSee Table ASee Table ASee Table ASee Table A
FrameBronze
ButtonBrass/Copper
Sealing AssemblyBeryllium Nickel w/Teflon
BulbGlass
Compression ScrewBronze
DeflectorCopper

Specifications as published by Tyco. Please confirm the exact model with us before ordering.

More Tyco Standard Spray Sprinklers

Fire Sprinklers from other brands

Savemax

Savemax Flexible Drop for Sprinklers (700 to 1800 mm)

Flexible dropSprinkler connector700 to 1800 mm

A flexible hose connector that links the rigid sprinkler branch pipe above a false ceiling to the sprinkler head below it. It takes up building movement, ceiling deflection and installation misalignment, so the head can be positioned without cutting or re-routing pipe.

View specifications ›

See all fire sprinklers ›

Ask price