Apollo Discovery Multi-Sensor Detector (CO/Heat)
Apollo logoAuthorised distributor for Apollo

Apollo Discovery Multi-Sensor Detector (CO/Heat)

58000-305APOCO and heatDiscoveryEN 54-5

An addressable detector that combines a CO detection cell and a thermistor heat sensor into one analogue value, responding to both smouldering and flaming fires.

  • Responds to smouldering and flaming fires
  • Less prone to false alarms from steam and dust
  • Five response modes
  • Remote test feature
  • 0 to 50°C, IP44
  • EN 54-5, with LPCB, VdS and CPR approvals, 5 year warranty

Standards and approvals: EN 54-5, LPCB, VdS, CPR

Ask price & availability

Specifications

Specifications
Specification58000-305APO
Warranty5 year
ApplicationsBedrooms, Hospitals, Hotels, Offices, University campuses, Warehouses
Fire TypeFast and slow burning fires
ColourWhite
Weight94.4g
Materials housingPolycarbonate
Materials terminalsNickel plated stainless steel
Product length54mm | 2.13in
Product diameter100mm | 3.94in
Detection principleTemperature sensitive resistance.Ambient carbon monoxide level.
Analogue value nominal25
Analogue value (- tolerance)2
Analogue value (+ tolerance)2
Analogue value25 +2/-2
Alarm level analogue value55
Protocol voltage5 to 9V peak to peak
Protocol voltage (max)9V
Protocol voltage (min)5V
Power-up surge current1mA
Maximum power-up time10 seconds
Status indicator: AlarmRed
Quiescent current400μA
Quiescent current tested at24V dc
Terminal functions L2+L2, Loop in & out positive
Terminal functions L1 in-L1 in, Loop (isolated) negative
Terminal functions +R+R, Remote indicator positive connection
Terminal functions -R-R, Remote indicator negative connection
PolarityL1 &, L2 are polarity sensitive
Humidity (max)90%, RH
Humidity (min)15%, RH
Humidity Noteno condensation or icing
Humidity15% to 90% (no condensation or icing)
Operating temperature0 to 50°C | 32 to 122°F
Operating temperature (max)50°C | 122°F
Operating temperature (min)0°C | 32°F
IP rating ValueIP44
Storage temperature (max)30°C
Storage temperature (min)10°C
Storage temperature10 to 30°C

Specifications as published by Apollo. Please confirm the exact model with us before ordering.

More Apollo Addressable Detectors

Apollo Soteria Heat Detector

SA5100-400APOHeatSoteria

An addressable heat detector with two heat sensors placed laterally for accurate detection in all orientations, and eight response modes for a wide range of application temperatures.

View specifications ›

Smoke and Heat Detectors from other brands

See all smoke and heat detectors ›

Ask price
Call +91 92440 89060Send a text messageEmail usWhatsApp us