HD Fire Jumbo Water Curtain Nozzle JCS, Stainless Steel, Flanged
Sizes: 65, 80 or 100 mm
A large stainless steel nozzle with a flanged end that throws a flat curtain of water upward, used to separate one area from another with a wall of water.
A water curtain, or drencher, puts a sheet of water across an opening so that fire and heat cannot pass through it. It is used where a fire wall cannot be built: large openings between floors, escalators, rolling shutters, windows close to another building, and gaps between plant. FPS designs, supplies, installs and maintains water curtain systems in Bhopal and across Madhya Pradesh, with nozzles from Tyco, HD Fire, Kartar Valves and Aaag.
| Large openings, shutters and escalators | Curtain nozzles |
|---|---|
| Windows and glazing | Window sprinklers |
| Separating plant or buildings | Jumbo curtain nozzle |
| The valve that releases it | Deluge valves |
Open curtain nozzles are set in a line along the top or bottom of the opening. Their deflectors spread the water flat, in a semicircular sheet, so the nozzles overlap into a continuous curtain. The water takes up and reflects radiant heat, cools the smoke and wets the surfaces on the protected side.
The nozzles are fed through a deluge valve, opened automatically by the fire alarm or by heat detectors near the opening, or by hand. Window sprinklers do a similar job on glazing: closed heads on the sprinkler system wet the whole glass so it holds back the fire, and open exposure sprinklers spray the outside of windows that face another building.
In India these systems are often called drenchers. A curtain on its own does not stop smoke, so it is planned together with the building's smoke control and fire alarm.
Aaag curtain nozzles in brass or stainless steel spread a flat semicircular curtain, K 23 to 72, for up to 10 bar, pendent over windows or horizontal to divide an area. HD Fire CN and CNS nozzles are UL Listed in K20 to K79, and its stainless steel JCS jumbo nozzle throws a large curtain upward from a flanged end. Kartar makes brass curtain nozzles in heavy and medium versions.
| Model | Key facts |
|---|---|
| HD Fire Jumbo Water Curtain Nozzle JCS, Stainless Steel, Flanged | Water curtain, Model JCS, Stainless steel, Flanged |
| HD Fire Water Curtain Nozzle, Models CN and CNS, UL Listed | Water curtain, ½ inch, K20 to K79, UL Listed |
| Kartar Valves Water Curtain Nozzle, Brass, 1/2 inch BSP (Heavy and Medium) | Water curtain, Brass, 1/2 inch BSP |
| Aaag Water Curtain Spray Nozzle, Brass (AAAG 291CB) | Water curtain, Brass, 10 bar, K 23 to 72 |
| Aaag Water Curtain Spray Nozzle, Stainless Steel (AAAG 291CS) | Water curtain, Stainless steel, 10 bar, K 23 to 72 |
Sizes: 65, 80 or 100 mm
A large stainless steel nozzle with a flanged end that throws a flat curtain of water upward, used to separate one area from another with a wall of water.
Sizes: 1/2″ BSPT/NPT
Non-automatic open outside sprinklers that protect windows, walls, steel beams, columns and roofs from exposure fire. Installed with the orifice slot pointing down, the spray absorbs and reflects heat radiation, and the nozzle is UL Listed.
Brass water curtain nozzles with a 1/2 inch BSP thread, listed in a heavy version (K920.WCH) and a medium version (K920.WCM). A water curtain nozzle spreads water in a flat sheet across an opening.
A brass nozzle that spreads water in a flat, semicircular curtain, used as a window spray nozzle when pendent or to separate the fire area when mounted horizontally.
The stainless steel water curtain nozzle, giving a flat, semicircular curtain for window protection or for separating the area on fire.
Tyco WS and CWS window sprinklers are closed, fast response heads listed to wet the whole surface of tempered, heat strengthened or ceramic glass windows, the CWS hidden behind a cover plate. Tyco Issue A and B exposure sprinklers spray the outside of a building's windows against a fire next door.
| Model | Key facts |
|---|---|
| Tyco Model WS Specific Application Window Sprinkler, Horizontal and Pendent Vertical Sidewall, K5.6 (TFP620) | Window sprinkler, Fast response, glass bulb, K5.6, Brass |
| Tyco Model CWS Concealed Window Sprinkler, Pendent Vertical Sidewall, K5.6 (TFP621) | Concealed window sprinkler, Fast response, solder link, K5.6, Brass |
| Tyco Issue A and B Window Type Exposure Protection Sprinklers (TFP835) | Exposure protection, Window sprinklers, Bronze, UL, FM |
Fast response glass bulb window sprinklers, listed to wet the entire surface of heat strengthened, tempered or ceramic glass windows using closed sprinklers.
A fast response, solder link concealed window sprinkler that sprays water across window glazing in a horizontal pattern, listed to wet the entire surface of heat strengthened, tempered or ceramic glass.
Sprinklers that spray water on window glazing on the outside of a building, at set spacings, to protect it from exposure fires.
Each curtain is fed through a deluge valve, opened by the fire alarm, heat detectors or a manual release beside the opening. The deluge system page compares the valves, skids and trim we supply.
Start with the opening: its width and height set the number of nozzles and their spacing, and the K factor and pressure set the water each one gives. The curtain must cover the full width, with overlap at the ends.
Decide the release: automatic from the fire alarm or heat detectors next to the opening, with a manual release beside it, through one deluge valve per curtain or zone.
Plan the water: all the nozzles of a curtain flow at once, so the pumps and tank are sized for every curtain that can operate together. We survey, design, install and test the system, and maintain it under an AMC.