ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
Supplier for Tyco

Tyco Special Application Sprinklers in Bhopal

Fire Protection System (FPS) supplies Tyco special application sprinklers in Bhopal: attic, window and combustible concealed space sprinklers, tamper resistant institutional sprinklers, flat spray and flush sprinklers, old style conventional sprinklers, corrosion resistant stainless and coated models, and high temperature Quartzoid sprinklers.

Where to use Special Application Sprinklers

  • Sloped attic spaces under combustible or non-combustible roofs
  • Heat strengthened, tempered or ceramic glass windows
  • Light hazard combustible and non-combustible concealed spaces
  • Correctional, detention and mental health care facilities
  • Suspended open ceilings and racks in systems designed to CEA 4001 or EN 12845
  • Offices, hospitals, schools, apartments and hotels with poured concrete or suspended ceilings (FSC flush sprinkler)
  • Restaurants, food service production areas, factories, refineries and chemical plants (stainless steel TY-L)
  • Commercial occupancies where corrosive atmospheres may exist
  • Areas with high ambient temperatures (Issue D Quartzoid)
  • Fur vaults, special construction features, and replacement of old style sprinklers installed before 1955

Tyco Special Application Sprinklers models

How to choose

Special application sprinklers are tested and listed for one kind of space or condition, and must be installed exactly as their data sheet says. Start with the space. In sloped attics, the BB, SD and HIP attic sprinklers throw long, narrow patterns along the roof, so in many cases fewer branch lines are needed than with standard spray sprinklers, and the AP covers attic areas outside their scope. For concealed spaces, the CC3 is a quick response upright sprinkler for light hazard combustible and non-combustible voids, on CPVC or steel pipe. For glazing, the WS (glass bulb) and CWS (concealed, solder link) window sprinklers are listed to wet the whole surface of heat strengthened, tempered or ceramic glass windows.

For prisons and similar buildings, the TFP PH2 (pendent), TFP PH5 (horizontal sidewall) and RAVEN models are tamper resistant, with flush designs that hide most or all of the working parts. The FSC is a quick response flush pendent for poured concrete or suspended ceilings, approved by VdS for CEA 4001 or EN 12845 systems. The TY-FRFS and TY-FS flat spray sprinklers, also for CEA 4001 and EN 12845 work, have a flatter pattern for low clearance above suspended open ceilings and in racks.

Conventional, or old style, sprinklers (Series TY-B and TY-FRB) throw about half their water up and half down. NFPA permits them where special construction needs that pattern, in fur vaults, or to replace similar sprinklers installed before 1955. The TY-B uses a 5 mm bulb and is standard response; the TY-FRB uses a 3 mm bulb and is quick response; TFP663 covers a VdS approved TY-B with a 4 mm bulb and special response.

For corrosive atmospheres, choose the TY-B and TY-FRB in stainless steel, SMO or titanium, the polyester coated Poly-Stainless versions, or the stainless steel TY-L; Tyco advises checking the material against the actual chemicals, temperatures and gas velocities on site. For high ambient temperatures, the Issue D Quartzoid comes in 204°C, 260°C and 343°C ratings. FPS supplies, installs and maintains Tyco sprinklers in Bhopal and across Madhya Pradesh.

Frequently asked questions

What does the K-factor of a sprinkler mean?
The K-factor is the discharge coefficient: the higher it is, the more water the sprinkler releases at a given pressure. The sprinklers on this page run from K4.2 to K8.0 in US units, and K57 to K115 in metric units for the European editions.
What is an old style or conventional sprinkler?
It is a sprinkler that can be fitted upright or pendent and sends roughly half its water upward and half downward in a spherical pattern. NFPA permits it where special construction needs that pattern, for fur vaults, or to replace similar sprinklers installed before 1955.
Which Tyco sprinklers are made for corrosive atmospheres?
The Series TY-B and TY-FRB in stainless steel, SMO or titanium (TFP680), the polyester coated Poly-Stainless versions (TFP682) and the stainless steel Series TY-L (TFP683). Tyco recommends confirming the material against the specific chemicals, temperatures and gas velocities on site.
What are institutional sprinklers?
They are tamper resistant sprinklers for correctional, detention and mental health care facilities, designed to reduce the chance of anyone using sprinkler parts to harm themselves or others. Tyco's models here are the TFP PH2, TFP PH5 and RAVEN.
Can sprinklers protect glass windows?
Yes. Tyco's Model WS and CWS window sprinklers are listed to wet the whole surface of heat strengthened, tempered or ceramic glass windows. In Tyco's furnace tests to the ASTM E119 time and temperature relationship, the protected window had to last two hours with no cracking or visible damage.
Does FPS supply Tyco special application sprinklers?
Yes. FPS supplies, installs and maintains Tyco sprinklers in Bhopal and across Madhya Pradesh. Prices are on request: call or WhatsApp +91 92440 89060.

More Tyco products

Call +91 92440 89060Send a text messageEmail usWhatsApp us