Notifier RP-2002(E) Conventional Releasing Control Panel
Notifier logoDealer for Notifier

Notifier RP-2002(E) Conventional Releasing Control Panel

Releasing panelConventionalSix zonesSeismic listingNFPA 13

A UL listed six-zone releasing panel for single and dual hazard deluge and preaction systems, with a seismic listing.

  • Designed for sprinkler standards NFPA 13, 15 and 16
  • Single or dual-hazard operation
  • Cross-zone (double-interlock) capability
  • Six programmable Style B (Class B) initiating device circuits
  • UL listed and FM approved, with CSFM, MEA and seismic listings

Standards and approvals: UL: S635, FM approved, CSFM: 7165-0028:0245, MEA: 333-07-E, Seismic Listing: Reference certificiate of compliance

Ask price & availability

Specifications

Specifications
SpecificationDetailsDetailsDetails
RP-2002 (FLPS-7 Power Supply)120 VAC, 60 Hz, 3.66 amps
RP-2002E (FLPS-7 Power Supply)240 VAC, 50/60 Hz, 2.085 amps
Wire sizeminimum 14 AWG (2.0 mm²) with 600 V insula- tion, supervised, nonpower-limited
Door19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR- CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Weight24.05 lbs. (10.9 kg)
Dimensions, Height 20.00" (50.80cm), Width 22.50" (57.15cm), Depth 8.50" (21.59cm)
Alarm Systems requirements, NFPA 12 CO2

Specifications as published by Notifier. Please confirm the exact model with us before ordering.