ISO 9001:2015 Certified · MSME Registered · Military Engineering Services Registered
Fire Protection System logoFIRE PROTECTION SYSTEMTMFire safety contractors, dealers & distributors · Bhopal, M.P.
EXCELLENCE IN FIRE EXTINGUISHER, FIRE HYDRANT, FIRE ALARM & FIRE SUPPRESSION SYSTEMS
System Sensor Multiple Input/Output Modules (CR-6, SC-6, CZ-6, IM-10)
Dealer for System Sensor

System Sensor Multiple Input/Output Modules (CR-6, SC-6, CZ-6, IM-10)

CR-6SC-6CZ-6IM-10Multi-way modules

Multi-way addressable modules for places where many single modules would otherwise be needed, each point with its own address set on rotary decade switches.

  • CR-6 six relay control, SC-6 six supervised control, CZ-6 six conventional zone, IM-10 ten input monitor
  • Supervise and activate sounders, strobes, door closers, call points and waterflow switches
  • CZ-6 monitors existing conventional two-wire detector zones in retrofit work
  • Individual LEDs; unused addresses can be disabled
  • Class A or B operation, removable plug-in terminal blocks
  • 15 to 32VDC, 0 to 50°C, CPR

Standards and approvals: CPR

Ask price & availability

Specifications

Specifications
SpecificationCR-6SC-6CZ-6IM-10
Operating Voltage Range15 to 32VDC15 to 32VDC15 to 32VDC15 to 32VDC
Maximum Wiring Resistance40 Ohms40 Ohms40 Ohms40 Ohms
Application Temperature Range-0°C to +50°C-0°C to +50°C-0°C to +50°C-0°C to +50°C
Humidity10% to 90% relative Humidity (non-condensing)10% to 90% relative Humidity (non-condensing)10% to 90% relative Humidity (non-condensing)10% to 90% relative Humidity (non-condensing)
Size173mm H x 147mm W x 32mm D173mm H x 147mm W x 32mm D173mm H x 147mm W x 32mm D173mm H x 147mm W x 32mm D
Min/Max Wire Gauge for Terminals1.0mm2 to 2.0mm21.0mm2 to 2.0mm21.0mm2 to 2.0mm21.0mm2 to 2.0mm2
Maximum Standby Current1.49mA (Blinking LED once every 5 seconds)2.34mA (Blinking LED once every 5 seconds)2.04mA (Blinking LED once every 5 seconds)3.50mA (Blinking LED once every 5 seconds)
Maximum Alarm Current36mA at 32V assuming all six relays have switched once and all six LEDs solid on36mA at 32V assuming all six relays have switched once and all six LEDs solid on40mA at 32V assuming all six LEDs solid on60mA at 32V assuming all ten LEDS solid on
Relay current30mA/relay pulse 15.6ms duration, pulse under panel control
Relay Contact Ratings3A at 30VDC Resisitive Load3A at 30VDC Resisitive Load
Maximum Supervising Line Resistance1000 Ohms
Maximum Loop Wiring Resistance40 Ohms or Max supervising line wiring resistance 25 Ohms
External Supply VoltageDC Voltage: 18 to 28V power limited | Ripple Voltage: 0.1V rms maximum. Current: 480mA at 24V (all six zones in alarm)
Maximum Supervising Line Wiring Resistance1000 Ohms
Maximum Line Voltage11.3VDC
Maximum Line Current240µA

Specifications as published by System Sensor. Please confirm the exact model with us before ordering.

More System Sensor Interfaces & Modules

Fire Alarm Interfaces and Modules from other brands

Apollo

Apollo Intelligent Input/Output Module

SA4700-102APOInput/OutputXP95, Discovery, CoreProtocol

A loop device that monitors single pole, volt-free contact inputs and controls relay output contacts, linking the fire panel to other equipment. It works with XP95, Discovery and CoreProtocol.

View specifications ›

See all fire alarm interfaces and modules ›

Ask price
Call +91 92440 89060Send a text messageEmail usWhatsApp us