Start with the type of system. The FPC-500 is a conventional panel: detectors are wired in zones and the panel shows which zone is in alarm. It comes in three sizes, FPC-500-2 with 2 zones for up to 64 detectors, FPC-500-4 with 4 zones for up to 128 detectors and FPC-500-8 with 8 zones for up to 256 detectors, with a plain text LCD for programming and operation and a 3 A power supply.
For an addressable system, the AVENAR panel 2000 is a compact modular panel for small to medium systems on LSN, Bosch's addressable loop bus. Each kit comes in a housing with the panel controller, power supply, battery controller module and one LSN loop module, and can grow to six functional modules, up to four of them LSN 0300 A loop modules with up to 254 LSN elements per loop. It supports addressable and conventional devices together, in stub or loop wiring, and modules are detected automatically when plugged onto the panel rail. Choose the wall-mount or frame-mount housing for the site.
Choose the license by function. The standard license covers network size and fire detection features. The premium license adds an evacuation button and evacuation zone monitoring on the AVENAR panel 2000, and on the FPE-8000-PPC controller for AVENAR panel 8000 it adds interfaces to building management systems, hierarchy panels and voice alarm systems, with individual control of evacuation zones and fire controls. The FPE-8000-FMR AVENAR keypad 8000 gives the same operation at a second location, or can act as a redundant panel controller.
FPS supplies, installs, programs, commissions and maintains Bosch fire panels in Bhopal and across Madhya Pradesh. The AVENAR panel 8000 controllers and keypad are configured with Bosch FSP-5000-RPS programming software. Confirm the exact kit, license and part numbers with FPS before ordering.