System Sensor InnovairFlex D2E Conventional Duct Smoke Detector
A conventional 2-wire photoelectric duct smoke detector with integrated low-flow technology and modular construction, fitted with a Series 300 conventional detector base.
Fire Protection System (FPS), a System Sensor dealer in Bhopal, supplies System Sensor InnovairFlex duct smoke detectors, conventional, addressable, 2-wire and 4-wire, together with DST sampling tubes sized to the duct. FPS installs, tests and maintains them on HVAC ducts across Madhya Pradesh.
A conventional 2-wire photoelectric duct smoke detector with integrated low-flow technology and modular construction, fitted with a Series 300 conventional detector base.
An intelligent, non-relay photoelectric duct smoke detector for addressable systems, fitted with a base for Series 200 intelligent detectors.
A 2-wire photoelectric duct smoke detector with a pivoting housing that fits square or rectangular footprints on round or rectangular ductwork.
A 4-wire photoelectric duct smoke detector for 120 VAC, with a pivoting housing, a Test/Reset button and a patented interconnect feature for multi-fan shutdown.
Steel sampling tubes with holes drilled along their length that carry duct air to the detector. Each size suits a range of duct widths, and the tube is bought separately from the detector.
A duct smoke detector draws a sample of air from an air conditioning or ventilation duct through a sampling tube and checks it for smoke, so smoke carried in the ductwork is picked up. All System Sensor models here are photoelectric InnovairFlex units with integrated low-flow technology and a plug-in sensor head, and they mount on round or rectangular ducts in a square or rectangular footprint.
Choose by the fire alarm system. The D2E is a conventional 2-wire detector fitted with a Series 300 conventional detector base and powered at 8.5 to 35 VDC. The DNRE is an intelligent, non-relay addressable detector fitted with a Series 200 base for addressable loops. The D2 is a 2-wire photoelectric detector rated for air speeds of 100 to 4,000 ft/min (0.5 to 20.32 m/sec). The D4120 is a 4-wire detector for 120 VAC, with a Test/Reset button and a patented interconnect feature for multi-fan shutdown.
Then choose the sampling tube. The DST tubes are ordered separately and must match the duct width: DST1 up to 0.3 m, DST1.5 for 0.3 to 0.6 m, DST3 for 0.6 to 1.2 m, DST5 for 1.2 to 2.4 m and DST10 for 2.4 to 3.7 m. The tube should reach at least 5/8 of the way across the duct and is always fitted with the air inlet holes facing into the airflow.
FPS supplies, installs and maintains System Sensor duct smoke detectors in Bhopal and across Madhya Pradesh.
Try "landing valve", "Apollo call point", "9 kg ABC" or a model code.
No products yet. Tap "Add to quote" on any product, then send the whole list to us in one WhatsApp message.